Features

SCR power chip with LTE technology Universal control voltage
Compact modular design complete with heat sink Burst firing  ( zero cross )
DIN-rail mountable LED status indicator
Buit-in varistor protection Problem-free specification according to industry standard
Operational current up to 50 A ( AC-1 ) IP 20 protection
Line voltage up to 600 V a.c. Easy and quick installation
General / Type ECI 15-1 ECI 30-1 ECI 50-1
Product description

ECI Electronic contactors are designed for applications demanding fast and precise switching. The contactors utilize SCR power chip with new LTE ( Low Thermal Expansion ) technology. This unique power chip design ensures high switching capacity and long life.The contactors are burst fired for reduced EMC emission, have LED status indicators and accept universal control voltages. The units are DIN-rail mountable, complete with heat sink and require no additional components.

Typical applications

ECI electronic contactors are designed for fast and demanding switching of loads such heaters, solenoids, transformers and motors.

Design standard

IEC/EN 60947-4-3

Approvals

CE, CSA and NRTL/C ( in compliance with UL 508 )

Output Specifications

Operational current

AC-1, AC-51 ( heater load )

AC-3, AC-53a ( motor load )

 

 

15 A

15 A 1

 

 

30 A

15 A

 

 

50 A

15 A

Operational Voltage

24-230 V a.c.

24-480 V a.c.

24-600 V a.c.

Leakage current max.

1 mA

Minimum operational current

10 mA

Semiconductor protection fusing

type 1 co-ordination

type 2 co-ordination

 

 

50 A gL/gG

1800 A2S1

 

 

50 gL/gG

1800 A2S

 

 

50 gL/gG

1800 A2S

Thermal specifications and environment

Power dissipation, continuous duty

1.2 W/A

Power dissipation, intermitent duty

1.2 W/A x duty cycle

Ambient temperature range

-5 to 40 oC

Cooling method

Natural convection

Mounting

Vertical ( see also general mounting instructions )

Max. ambient temperature with limited current

60 oC

Storage temperature range

-20 to 80 oC

Protection/pollution  degree

IP 20/3

Insulation specification
Rated insulation voltage, Ui

660 V

Rated impulse withstand voltage, Uimp

4 KV

Insulation category

III

Control specification
Control voltage ( +/- 10% )

5-24 V d.c. / 24-230 V a.c./d.c.

Pick-up voltage

4.25 V d.c. / 20.4 V a.c. / d.c.

Drop-out voltage

1.5 V d.c. / 7.2 V a.c. / d.c.

Control current/power max.

15 mA at 24 V d.c. / 1.5 VA/6mA at 24 V d.c.

Response time max.

1/2 cycle  / 1 cycle

EMC immunity

Meets requirements of EN50082-2

ECI 1

1) Contactors designed for 600 V: Max. AC-3 load: 10 A Max. type 2 co-ordination fuse: 450 A2S

Operational current max. AC-1 Control voltage Dimensions Type Operational voltage
24-230 V a.c. Code # 24-480 V a.c. Code # 24-600 V a.c. Code #
15 A 5-24 V d.c. 22.5 mm module ECI 15-1 037N0063 037N0065 037N0067
15 A 24-230 V a.c./d.c 22.5 mm module ECI 15-1 037N0064 037N0066 037N0068
30 A 5-24 V d.c. 45 mm module ECI 30-1 037N0007 037N0009 037N0011
30 A 24-230 V a.c./d.c 45 mm module ECI 30-1 037N0001 037N0003 037N0005
50 A 5-24 V d.c. 90 mm module ECI 50-1 037N0008 037N0010 037N0012
50 A 24-230 V a.c./d.c. 90 mm module ECI 50-1 037N0002 037N0004 037N0006

ECI Wiring diagram

Operating at high temperatures

If the contactor is placed inside small cabinets, care must be taken to avoid exceeding the max. ambient temperature. Otherwise the current must be derated according to table.

Ambinet temperature ECI 15 ECI 30 ECI 50
40 oC 15.0 A 30.0 A 50.0 A
50 oC 12.5 A 25.0 A 40.0 A
60 oC 10.0 A 20.0 A 30.0 A